4.3.2
Mains connection, DC supply
Note!
ƒ
ƒ
Shield sheet installation
Stop!
ƒ
ƒ
M6
M5
Fig.4-2
EDKVS9332X DE/EN/FR 2.0
Basic devices in the power range 0.37 ... 11 kW
If a mains filter or RFI filter is used and the cable length between mains/RFI
filter and drive controller exceeds 300 mm, install a shielded cable.
For DC-bus operation or DC supply, we recommend using shielded DC
cables.
To avoid damaging the PE stud, always install the shield sheet and the PE
connection in the order displayed. The required parts are included in the
accessory kit.
Do not use lugs as strain relief.
0
1
2
3
4
5
6
7
Installation of shield sheet for drive controllers 0.37 ... 11 kW
PE stud
Screw on M5 nut and tighten it by hand
Slide on fixing bracket for shield sheet
Slide on serrated lock washer
Slide on PE cable with ring cable lug
Slide on washer
Slide on spring washer
Screw on M5 nut and tighten it
Screw shield sheet on fixing bracket with two M4 (a) screws
Electrical installation
Mains connection, DC supply
a
a
1.7 Nm
L3 +UG -UG
L1
L2
15 lb-in
PE
http://www.DataSheet4U.net/
M5
PE
3.4 Nm
30 lb-in
4
8
7
4
2
0
}
PE
+
9300vec130