Electrical installation
Basic device with a power of 45 kW
Motor connection
Features of the connection for motor temperature monitoring:
Pins X7/8, X7/9 from resolver input (X7), or
pins X8/8, X8/5 from incremental encoder input (X8)
Connection
Tripping point
Comments
}
0
T1
T2
Fig.4-19
Cable cross-sections
9300
Type
EVS9330-xx
164
Linear KTY temperature sensor
Warning: adjustable
Error (TRIP): fixed at 150 °C
Monitoring is not active in the Lenze setting.
The KTY temperature sensor is monitored with regard to interruption and short
circuit.
M8
U, V, W,
PE
+
15 Nm
PE
132 lb-in
PE
U
V
W


M5 x 12
3 Nm (26.5 lb-in)
Motor connection with KTY thermal sensor
PE stud
Connection of PE cable with ring cable lug
U, V, W
Connection of motor cable with ring cable lugs
Observe correct polarity. Observe maximum length of motor cable.
Shield clamps
Connect shields of motor cable with a surface as large as possible to the shield sheet and
fasten with shield clamps and M5 × 12 mm screws
Cable ties
Strain relief of motor cable
2
[mm
]
70
1
2
3
http://www.DataSheet4U.net/
Cable cross-sections U, V, W, PE
9300vec124
[AWG]
2/0
EDKVS9332X DE/EN/FR 2.0
datasheet pdf - http://www.DataSheet4U.net/