Lenze EVS9321 Instructions De Montage page 160

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4
Electrical installation
Basic device with a power of 45 kW
Mains connection, DC supply
Fuses and cable cross-sections for the DC supply
Stop!
ƒ
ƒ
9300
Type
EVS9330-xx
1)
The specifications are recommendations. Other designs/laying systems are possible.
The cable cross-sections apply under the following conditions: Use of PVC-insulated copper leads, conductor
temperature < 70 °C, ambient temperature < 40 °C, no bundling of cables or cores
The cable cross-section is limited by the cable entries at the drive controller.
2)
The rated currents of the fuses EFSGR0xx0AYHx and EFSGR0xx0AYIx of Lenze are given. When using other fuses,
other fuse currents and cable cross-sections may arise.
National and regional regulations must be observed
160
Only use semiconductor fuses.
On principle, fuse DC cables as 2-pole (+U
DC fuse 14 × 51
(EFSGR0xx0AYHx)
2)
Rated fuse current
[A]
, -U
).
G
G
DC fuse 22 × 58
Installation in
accordance with
(EFSGR0xx0AYIx)
EN 60204-1
2)
Rated fuse current
Laying system
B2
[A]
[mm
2 × 100
http://www.DataSheet4U.net/
Installation in
accordance
1)
with UL
+U
, -U
+U
, -U
G
G
G
G
C
2
2
]
[mm
]
[AWG]
2 × 35
2 × 1
EDKVS9332X DE/EN/FR 2.0
datasheet pdf - http://www.DataSheet4U.net/

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Evs9332

Table des Matières