No.
Designation
5.1.0.0
Multi pump
5.1.1.0
Operating mode
5.1.2.0
Setting, MA/SL
5.1.3.0
Pump cycling
5.1.3.1 Manual pump
cycling
5.1.3.2 Internal/external
5.1.3.3 Internal: Time
interval
5.1.4.0
Pump enabled/
disabled
5.1.5.0
SSM
5.1.6.0
SBM
5.1.7.0
External off
5.2.0.0
BMS
5.2.1.0
LON/CAN/
IF-Module
Wink/service
5.2.2.0
Local/remote
operation
Installation and operating instructions Ixens, Ixens-D, Ixens Bloc
Type
Symbol Values/explanations
Double pump
±
Main/standby operation
Parallel operation
±
Manual converting from master
to slave mode
±
Carries out pump cycling inde-
pendent of the countdown
±
Internal pump cycling
External pump cycling
±
Can be set between 8 h and 36 h
in 4 h steps
±
Pump enabled
Pump disabled
±
Individual fault signal
Collective fault signal
±
Individual readiness signal
Individual run signal
Collective readiness signal
Collective run signal
±
Individual external off
Collective external off
Settings for Building Manage-
ment System (BMS) – building
automation
±
The wink function permits the
identification of a device in the
BMS network. A "wink" is exe-
cuted by confirmation.
±
BMS local operation
BMS remote operation
English
Display conditions
Only displayed when DP is
active (incl. sub-menus)
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master, see "AUX" ter-
minal
Displayed when internal
pump cycling is activated
Only displayed for double
pump master
Only displayed for double
pump master
Is only displayed for double
pump master and SBM func-
tion at readiness/operation
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Only displayed for double
pump master
Incl. all sub-menus, only dis-
played when BMS is active
Only displayed when LON,
CAN or IF-Module is active
Temporary state, automatic
reset to remote operation
after 5 min
105