LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 6350A the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate
Marking
Standards: IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-15 : 2010
T6: -40ºC to 60 ºC
T5: -40°C to 75 °C
T4: -40ºC to 85 ºC
Terminal:
41-44 and 51-54
Ex nA [ic]
Uo=5.7 V
Io=8.4 mA
Po=12 mW
Co=40 μF
Lo=200 mH
Terminal :
13,14 and 23,24
Ex ic:
Ii = ±100 mA
Revision date:
2014-12-15
IECEx Installation drawing
IECEx DEK 14.0071X
Ex nA [ic] IIC T6 Gc
Ex ic IIC T6 Gc
Ex ic IIIC Dc
CH1
41
14
42
13
43
12
44
11
CH2
51
21
52
22
53
23
54
24
6350A
CH1
41
14
42
13
43
12
44
11
CH2
51
21
52
22
53
23
54
24
6350A
Version Revision
V2R0
WWW.PRELECTRONICS.COM
(max): 32V
Terminal:
11,12 and 21,22
Ex nA
Umax = 32 VDC
Ex ic:
Ui = 32 VDC
Ci = 2 nF, Li = 1 μH
FNICO :
17.5 V
Ci = 2 nF, Li = 1 μH
6350104-FR
6350QI02
Page:
1/2
17