LERBAKKEN 10, 8410 RØNDE DENMARK.
Non Hazardous Location
Associated Apparatus
Barrier or FISCO Supply
With entity Parameters
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
Applicable for 6350B2a where
a = A (Single Channel) or
B (Double Channel)
All drawings are shown for Double
Channel. For Single Channel
installation Channel 2 (CH2) is not
mounted (terminal 51-54 and 21-24)
In each segment only one active device,
normally the associated apparatus is
allowed to provide the necessary energy
for the fieldbus system. All other
equipment connected to the bus are not
allowed to provide energy to the system.
Separately powered equipment needs a
galvanic insulation to assure that the
intrinsic safe fieldbus circuit remanis
passive.
See Installation notes
Terminal
13,14 and 23,24
Vmax (Ui)
30 V
Imax
(Ii)
140 mA
Pmax (Pi)
1 W
Ci
0
Li
0
Revision date:
2014-12-11
Hazardous (Classified) Location
Class I, Division 2, Group A,B,C,D
Class I, Zone 1, AEx ib IIC
14
13
12
11
21
22
23
24
14
13
12
11
21
22
23
24
14
13
12
11
21
22
23
24
Terminal
11,12 and 21,22
30 V
17.5 V
250 mA
any
5.32 W
any
2 nF
2 nF
1 H
1 H
Version Revision
V3R0
WWW.PRELECTRONICS.COM
Class I, Division 1, Group A,B,C,D
Class I, Zone 0, AEx ia IIC
CH1
41
42
43
44
CH2
51
52
53
54
6350B
CH1
41
42
43
44
CH2
51
52
53
54
6350B
CH1
41
42
43
44
CH2
51
52
53
54
6350B
Approved
Termination
Terminal
41-44 and 51-54
Vt or Uo
It or Io
Pt or Po
Ca or Co
La or Lo
6350104-FR
6350QE02
5.71 V
8.4 mA
12 mW
40 F
200 mH
Page:
2/6