The 6350 Series are Approved for Class I, Zone 0, applications. If connecting AEx[ib]
associated Apparatus or AEx ib I.S. Apparatus to the 6350 the I.S. circuit is only suitable for
Class I, Zone 1, or Class I, Zone 2, and is not suitable for Class I, Zone 0 or Class I, Division
1, Hazardous (Classified) Locations.".
9.
No revision to drawing without prior FM / CSA Approval.
10. Simple Apparatus is defined as a device that neither generates nor stores more than 1.2V,
0.1A 20uJ or 25mW.
11. The termination must be NRTL approved, and the resistor must be infallible.
12. Warning:
For applications in Div2 or Zone 2 (Classified Locations) Explosion hazard: Except for field
circuits, do not disconnect the apparatus unless the area is known to be non hazardous.
13. Warning:
Substitution of Components May Impair Safety.
Revision date:
2014-12-11
WWW.PRELECTRONICS.COM
Version Revision
V3R0