Fault messages via the indi-
cating/adjustment module
Exchanging the cable/rod
LEVEL TRANSMITTER 8185 - 4 ... 20 mA/HART
In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
?
E013
l
no measured value available
à
sensor in boot phase
à
sensor does not find an echo, e.g. because of faulty
installation or incorrect parameter adjustment
à
Wrong sensor length entered
?
E017
l
Adjustment span too small
à
Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E036
l
no operable sensor software
à
Carry out a software update or send the instrument for
repair
?
E042/E043
l
Hardware error, electronics defective
à
Exchange instrument or return instrument for repair
7.3 Exchange or shorten cable/rod
The cable or rod (meas. part) of the probe can be shortened, if
necessary. To loosen the meas. part you need two fork
spanners with spanner width 8.
1 Loosen the meas. part on the flat surfaces with a fork
spanner (SW 8), provide counterforce with another fork
spanner (SW 8)
2 Unscrew the loosened measuring part manually
3 Place the enclosed new double washer onto the thread.
Caution:
Make sure that the two components of the double washer
remain together.
4 Screw in a new measuring part manually
Maintenance and fault rectification