Set up with the indicating and adjustment module
Carrying out min. adjustment
Carrying out max. adjustment
22
Caution:
If there is a separation of different liquids in the vessel, e.g. by
condensation, LEVEL TRANSMITTER 8185 will always detect
the medium with the higher dielectric value.
Keep in mind that interfaces can cause faulty measurements.
If you want to measure the total height of both liquids, please
contact our service department or use an instrument for
interface measurement.
Start your parameter adjustment with the following menu items
of the basic adjustment:
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
Basic adjustment
Display
Diagnostics
Service
Info
2 Select the menu item "Basic adjustment" with [->] and
confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.
Min. adjustment
0.00 %
=
10,000 m(d)
8,000 m(d)
3 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the appropriate distance value in m (corresponding
to the percentage value) for the empty vessel (e.g. distance
from the sensor to the vessel bottom).
5 Save the settings with [OK] and move to "Max. adjustment"
with [->].
Proceed as follows: