Mounting
Socket
12
Fig. 5: Installation in concrete silo
Avoid using vessel sockets, i.e. mounting bosses. If possible,
mount the sensor flush with the vessel top. If this is not
possible, use short sockets with small diameter.
Higher sockets or sockets with a bigger diameter can generally
be used. They simply increase the upper dead band. Check if
this is relevant for your measurement.
Fig. 6: Mounting socket
LEVEL TRANSMITTER 8185 - 4 ... 20 mA/HART
ø >160 mm
19
ø >(6
/
")
64
d
DN40 ... DN150
> DN150 ... DN200
d
h
≤ 150
≤ 100