LEVEL TRANSMITTER 8185 - 4 ... 20 mA/HART
Make sure that the probe is not subjected to strong lateral
forces. Mount LEVEL TRANSMITTER 8185 at a position in the
vessel where no disturbances, e.g. from filling openings,
agitators, etc., can occur.
Fig. 7: Lateral load
If the probe can touch the vessel wall during operation due to
product movements or agitators etc., the measuring probe
should be fixed securely.
There is a thread (M12) in the gravity weight, e.g. for a lug.
Make sure that the probe cable is not completely taut. Avoid
tensile loads on the rope.
Avoid undefined cable-vessel connections, i.e. the connection
must be either grounded reliably or isolated reliably. Any
deviation from this requirement can lead to measurement
errors.
Mounting
13