Technical Data; What To Do If - Becker Wind-Automatic WA10 Notice De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Assembly and Operating Instructions
Nominal voltage
Switched current
System of protection
Protection class
(In accordance with the
assembly specifications)
Permissible ambient temperature
Type of installation
Dimensions (W x H x D)
Problem
Drive is not functioning.
Drive moves in the
wrong direction.
LED flashes slowly
LED flashes quickly
Subject to technical changes without notice.
14

Technical data

What to do if...?

Cause
Faulty connection.
Faulty connection.
Gust of wind
Line break
230-240 V AC / 50-60 Hz
5 A /250 V AC FOR cos ϕ =1
IP 44
II
-25 to +55 °C
Surface mounted
130 x 95 x 58 mm
Remedy
Check the connection.
Exchange s and t
wires in the power
supply unit.
Wait approx. 15 mins
Check the line, replace
if necessary.