Pipe Work; Electrical Connection / Earthing; Terminal Strip Positionning For Star (Y) And Delta () Connection (Multi-Voltages Electric Motors); Lower Voltage :  Connection - Samson NESE Manuel D'installation Et Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

  ENGLISH  
 
 
 
7.2 PIPE WORK 
Pump connection flanges are plugged to avoid any contamination during 
transport and storage. Protective covers should be removed only before 
installing  the  pump  in  the  piping.  Remove  dust  before  removing  the 
covers  from  pump  flanges.  Especially  for  new  pipe  work  :  clean 
thoroughly piping before connecting it to the pump. 
 Remove protective covers 
 Add flange gaskets 
 Fasten suction pipe 
 Fasten discharge pipe 
 
No stress must be applied to the pump casing by the pipe work. If 
 
excessive,  those  forces  and  moments  cause  misalignment, 
overheating of bearings, coupling wear, vibrations and possible failure or 
explosion of pump casing. 
After  replacement  of  a  pump  or  during  connection  of  pipes  to 
 
pump flanges, never use pump flanges as a support to pull or push 
the pipe works. 
 
The  axial  displacement  of  expansion  coupling  (if  installed)  should  be 
limited. Use tie rods as recommended by the manufacturer. 
 
Two designs are possible for the suction line : positive suction head and 
suction lift operation. 
 
Positive suction head operation : 
Nominal  diameter  of  the  pipeline  is  often  larger  diameter  than  pump 
suction flange. Unequal nominal diameter should be compensated by an 
eccentric  transition  part.  It  is  recommended  to  install  a  straight  pipe 
before  the  pump  inlet  (size  L  should  be  2  to  3  times  the  pipe  nominal 
dimension).  The  suction  line  should  be  laid  with  a  downward  slope 
toward the pump. 
Discharge pipe : 
Nominal diameter of discharge pipe should be chosen to ensure a max 
flow speed of 3m/s. 
 
Filter : 
If  required  a  filter  can  be  installed  before  the  pump  intake.  To  ensure 
proper working of pump the equivalent exchange surface of the strainer 
should be 3 time the pipe sectional area. 
Clogging level of filter should be checked regularly. 
 
 
 
Valves : 
It is advised to install isolating valves on suction and  discharge side for 
maintenance purpose. Those valves should be of large passage type and 
could be locked in position. 
Isolating valve on suction side should not be connected to pump suction 
flange. 
 
Non‐return valve : 
A  check  valve  can  be  installed  on  discharge  side  to  protect  the  pump 
from back flow effects such as pressure surges or back flow when pump 
is stopped. 
 
After  pipe  work  is  done  turn  pump  shaft  by  hand  and  check  it  turns 
freely.  If  it  appears  that  it  is  difficult  to  turn  pump  shaft,  then  check 
forces applied by piping to pump casing. Installation of piping should be 
done again. 
 
 
Location of connections : 
Connections : 
V = vent connection G1/8'' 
G = grease filling connection G1/8'' 
 
7.3 ELECTRICAL CONNECTION / EARTHING 
drive  to  motor  destruction  if  terminal  strip  are  positioned  in  a  wrong 
way. 
national and international regulations. 
 
proper type and size of electric cable. 
are  usually  indicated  inside  motor  junction  box).  Sensors  will  be 
connected  in  compliance  with  the  instructions  given  in  dedicated 
instruction manual. 
 
7.3.1
Multi‐voltage winding for voltages  230/400V and 400/690V :  
 
6 wiring terminals : 
 
To  change  motor  direction  of  rotation  reverse  two  phases  on  wiring 
terminals. Connection of earthing terminal is mandatory. 
 
7.3.2
Voltage : U 
12 
 
Check  that  motor  winding  corresponds  to  site  electric  power 
supply characteristics before electrical connections are performed. 
Connecting  a  230/400V  motor  on  a  400V  power  supply  or 
connection  of  a  400/690V  motor  on  a  690V  power  supply  might 
Electrical connection should be performed by qualified personnel 
only  having  necessary  agreements  and  in  compliance  with  local, 
Equipments used in an ATEX zone will be connected in compliance 
with CEI60079‐14. It is the responsibility of the end user to select 
Respect  motor  manufacturer  instructions  to  make  electric  motor 
connection (refer to the instructions supplied with the motor. they 
TERMINAL  STRIP  POSITIONNING  FOR  STAR  
(Y)  AND  DELTA  () CONNECTION  (MULTI‐
VOLTAGES ELECTRIC MOTORS) 
LOWER VOLTAGE :  CONNECTION 
 
 
 

Publicité

Chapitres

Table des Matières
loading

Table des Matières