Signal from gateway override function
Signals can be received from an override function via DANBUSS. When the signal is
received, there is change-over to night operation.
Settings:
Definition of function:
Day / Night =
0: No night setback
1: Night operation according to signal at S6 input
2: Night operation according to internal time clock
3. Night operation according to signal from the gateway's override function
Common Controller
Function description RC.8A.R1.02 © Danfoss 10/2001
Day/Night Ctrl. Settings
___
Day / Night
___
Mo day h
___
Mo night h
___
Tu day h
___
Tu night h
___
We day h
___
We night h
___
Th day h
___
Th night h
___
Fr day h
___
Fr night h
___
Sa day h
___
Sa night h
___
Su day h
___
Su night h
AKC 114G