2) The sensor is placed in the outlet air from the evaporator.
Required cut-out temperature = CutOut°C.
Required differential = Diff. K.
If night setback is required, define this by putting day/night in position ON.
If position ON is selected, the setback value must be set.
3) Two sensors are mounted. One on either side of the evaporator (weighted control).
The measured values are weighted with a percentage of S3 (air inlet) and a percentage of
S4 (air outlet).
Example:
S4 measures -25°C and S3 measures -20°C.
Required as regulation parameter is a weighted average consisting of 60% S4 and the rest
from S3 (only the S4 share is programmed). This gives a regulating value of på 0.6 x -25°C
+ 0.4 x -20°C = -23°C
Required cut-out temperature = CutOut°C.
Required differential = Diff. K.
Required S4 sensor influence = S4 Day %. (S3 is weighted automatically).
If night setback is required, define this by putting day/night in position ON.
If position ON is selected, the setback value must be set.
Furthermore sensor S4's influence during night operation must be set.
Function description RC.8A.R1.02 © Danfoss 10/2001
Thermostat Ctrl. Settings
2
Ther. Sx =
CutOut ° C ___
Diff. K ___
OFF / ON
Day/Night
Dt Night ___
3
Ther. Sx =
CutOut ° C ___
Diff. K ___
S4 Day % ___
S4 Night % ___
OFF / ON
Day/Night
Dt Night ___
AKC 114G