AKC 114G
Night operation
Change between day and night operation can be accomplished by means of an external
signal, by means of a time schedule in the controller or by means of a signal from the gate-
way's override function.
External signal
A signal connected to input "S6".
The input registers the resistance value of the connected sensor / contact function.
(A resistance value greater than 1400 ohm will give night operation, a resistance value
smaller than 1100 ohm will give day operation).
A light-sensitive sensor placed in the refrigeration appliance may be used as signal
transmitter.
The function can also be obtained by connecting an external relay.
A shortcircuited S6 input will give day operation.
The relay contact must be goldplated.
Internal time schedule
The start and stop times are set for each day of the week.
Principle
Definitions
Night: The moment when night operation starts
Day: The moment when night operation stops
Night = 0 or Day = 0:
When one of the two times is set at 0, or when both are set at 0, there will be no night
operation for that particular 24-hour period.
Night = 1 and Day = 1:
When the two settings are set to the same time, there will be night operation during the
entire 24-hour period.
Function description RC.8A.R1.02 © Danfoss 10/2001