Subcooling regulation

AKC 114G
Measurement of subcooling
Measurement can take place in one of the following two ways:
1) AKS 32R and S4
The measurement provides information about the exact subcooling value. (S3 to be
mounted. It becomes involved in the regulation if the pressure transmitter becomes defec-
tive).
2) S3 and S4
This measurement only provides information about the temperature difference above the
subcooling unit. The function will lower the liquid temperature with the set value.
Setting
Define here the function the controller is to have:
0.
Hotgas regulation
1.
Subcooling regulation, as described above under 1
2.
Temperature drop regulation, as described above under 2
SubCool Controller
SubCool Settings
If the subcooling function is selected, the pressure transmitter must be connected as follows:
Function description RC.8A.R1.02 © Danfoss 10/2001
SubCoolCtrl __ (0/1/2)
AKS 32R
-1 to 34 bar
DIN 43650 plug,Pg 9
1/4 flare:
060G0090
15