t
= 0 - +55°C
amb
230 V a.c., 50/60 Hz
2.5 VA
10 V < U < 256 V
DO1. Refrigeration *
DO2. Defrost *
DO3. Fan or
refrigeration 2 *
DO4. Alarm, light, rail heat
or hotgas defrost *
* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept.
** Gold plating ensures make function with small contact loads
*** UL-approval based on 30000 couplings
Koordineret afrimning
Coordinated defrost
RI8MB653 6-2015
INSTRUCTIONS
AK-CC 210
CE (250 V a.c.)
UL *** (240 V a.c.)
10 A Resistive
8 (6) A
5FLA, 30LRA
10 A Resistive
8 (6) A
5FLA, 30LRA
6 A Resistive
6 (3) A
3FLA, 18LRA
131 VA Pilot duty
4 (1) A
4 A Resistive
Min. 100 mA**
131 VA Pilot duty
Data communication
Type: Pt 1000 (1000 Ω /0°C ) /
Ptc 1000 (TYPE) /
NTC-M2020 (5000 Ω / 25°C)
( o06)
LON RS485
MOD-bus