Fan; Installation; Installing Housing - Maico ECA 100 ipro Instructions De Montage Et Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

UK │ 8. Installation preparations

8.4 Fan

NOTICE
Damage to unit/functional problems
in the event of rubbing impeller [2].
 Do not fit connecting flange so it is
twisted or crushed. Make sure there is a
level seating.
1. Unpack ECA and remove cover [6].
Unlock locking hooks ( arrow) with
screwdriver to loosen cover.
2. Fit foam strip supplied to connector in
centre.
The foam strip must be fitted to
ECA 100 ipro H and KH such that
the units do not draw in any
unwanted air from outside.

9. Installation

For installation with window installa-
tion kit FE 100/1 or spacing frame
ECA-DR  dedicated mounting
instructions.

9.1 Installing housing

1. Insert housing [1] into wall breakthrough/
wall sleeve (TOP must be at top).
18
2. Align housing horizontally and mark the
two dowel holes ( arrows).
3. Remove housing [1], drill M6 dowel holes
with a Ø of 6 mm and insert dowels.
4. Push cable grommet [3] carefully out of
housing and remove.
NOTICE
Danger of short circuits and damage to
unit. Water will penetrate if the power
cable is incorrectly fed into the fan
housing or if the cable grommet is not
fitted correctly.
 Cut off cable grommet cap [3] such that
the cable grommet fits tightly round the
power cable. Cut off at least 5 mm of the
cap (power cable can bend better and
electronics cover [4] can be positioned
correctly).
 Fit cable grommet [3] correctly, seal on
both sides if required.
5. Insert cable grommet [3] into housing.