6.1 Wall
The prescribed minimum distances
between the wall and the ceiling
shown in the figure must be
observed.
1. Make sure the housing has a level base.
2. Fit wall breakthrough or drill core hole.
Minimum diameter, 105 mm.
Recommendation: Fit wall sleeve
WH 100. Fit wall breakthrough with a
minimum diameter of 115 mm.
Use mounting plate ZM 11 for
rectangular wall breakthroughs.
3. Lay power cable (recessed) up to place of
installation, see above for spacing. Guide
the power cable at least 110 mm from
the wall.
16
6.2 Ceiling
Danger of short-circuits and
NOTICE
damage to unit if conden-
sation builds up in the fan
housing.
Thermally insulate ventilation
ducts in professional manner.
Allow for a condensation drain or
condensate collector in the riser.
Perform installation preparations as
described in Chapter 6.1.
6.3 Duct
1. Debur edges on the inside of the duct.
2. Perform installation preparations as
described in Chapter 6.1.
6.4 Fan
1. Unpack ECA and remove cover [6].
Unlock locking hooks ( arrow) with
screwdriver to loosen cover.
2. Fit foam strip supplied to connector in
centre.
The foam strip must be fitted to
ECA 100 ipro H and KH such that
the units do not draw in any
unwanted air from outside.