After choosing the parameter press key (18)
NUMBER OF PUMPS 3
PILOT PUMPS YES
- Line n. 1 NUMBER OF PUMPS
+
With keys (16)
number of the main pump which comprise the unit (maximum 4). In the example 3.
After selecting the parameter press key (18)
- Line n. 2 PUMP PILOT
+
With keys (16)
YES
means that the unit has a smaller pump
NO
hat the unit is composed only of equal sized pumps
In the example the unit has a smaller pump
After choosing the parameter press key (18)
COMPRESSOR NO
- Line n. 1 COMPRESSOR
+
With keys (16)
YES
means that the unit has a pump and an air compressor operated by the same switchboard
In the example NO
- Line n. 2 no message
After choosing the parameter press key (18)
DELAY FC.S. 40
ACTIVATION.FC.s.X60
- Line n. 1 DELAY FC.S.
Means that the function OUT OF CURVE (alarm and sequential start of all the pumps) will occur XXX seconds after
the closing of the minimum pressure bulb contact (off-the-shelf only in the conventional fireproof units PTA... STA....)
- Line n. 2 ACTIVATION FC.S.
Means that the function OUT OF CURVE will remain enabled for XXX seconds after the opening of minimum pressure
bulb contact. In the case of this example its for 60 seconds.
After choosing the parameter press key (18)
TIMING
PUMP N.1 S.060
- Line n. 1 TIMING
No parameter
- Line n. 2 PUMP N. 1 s.
+
With keys (16)
This means that the pump will be stopped XXX seconds after having reached the maximum pressure set.
In the case of this example it is for 60 seconds.
26
ENTER
-
or (17)
it is possible to set the last parameter to the value corresponding to the
ENTER
-
or (17)
it is possible to set YES or NO.
ENTER
-
or (17)
it is possible to set the parameter YES or NO
ENTER
ENTER
-
or (17)
it is possible to set the parameter to anything between 0 and 255 seconds
the following message will appear:
the following message will appear:
the following message will appear:
the following message will appear: