SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
Assembly
TRZ Plus and TRZ Plus Comfort
Mount the control panel with suitable plugs and screws through the mounting
holes on the backside of the control panel. No overhead installation or
rotated by 180 ° mounting.
The integrated display has to be mounted exactly 1.40 m high from the ground.
Note: The Control panel is also available with a UP-mounting kit.
Inserting the rechargeable batteries (TRZ Plus and TRZ Plus Comfort)
1.
Remove battery cover
2.
The batteries of adjacent wiring diagram
connected in series and connect (connection diagram on.
Battery cover included)
3.
Install the battery cover
Attention: Ensure the correct polarity on the
batteries!
Compact control panel 2A
Wall mounting :
1.
First remove the baseplate with control electronics.
2.
Fix the housing through mounting holes with suitable
plugs and screws to the wall.
3.
Encase the baseplate back.
Note: The control system must be fitted in a dry area at a place that is easily visible and accessible.
No overhead installation or rotated by 180 ° mounting.
The control system must not be hidden by wall projections, doors or structures.
Assembly:
Once the housing has been fastened to the wall:
1.
Insert ventilation plug on the underside of the housing
Note: Operating the control system without the
ventilation plug can lead to malfunction and is not
permitted!
Take care that the ventilation plug
is not covered by the rechargeable batteries!
Attention: Start up procedure of the control panel only with installed plexiglass cover.
Note: The Control panel is also available with a UP-mounting kit.
70
SMOKE VENT
TRZ Plus Comfort
Sicherungsübersicht
Fuse layout
Legende /
Key
:
F1 Netzsicherung /
mains fuse
F2 Motorsicherung /
motor fuse
F3 Akkusicherung /
battery fuse
Akkulageplan
Akustische Störmeldung
Battery connection diagram
Malfunction message beep-code chart
Beep Code, LED
(gelb /
yellow
)
Akkuverbindungskabel
0 > ---------------- OK
Battery cable
+
+
1 >
1--------1-----Netzausfall /
mains failure
2 >
1-1------------Störung Akku /
battery malfunction
3 > 1-1-1--------- Störung RWA-Bedienstelle /
malf. SHE manual call point
-
-
4 > 1-1-1-1-------Störung autom. Melder /
malfunction detector
5 > 1-1-1-1-1-----
S törung Motorüberwachung /
malf. motor monitoring circuit
-
-
+
+
Bottom part of housing
TRZ Plus
Battery cover
Batterys
Ventilation
plug