SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
Cable length diagram
To determine the necessary cable cross-sections as a function of the line length and the sum of the rated currents of the
drives.
Cable length diagram up to 2 amps for drives with a current draw < 2.5 A
Nominal drive current in amps
Cable cross-section determination
Notes re-cable cross-section determination and cabling layout
Simplified formulae for cable cross-section determination (for drives up to 2.5 amp nominal current draw)
Note: Permissible current supply of the TRZ Plus has to be considered, see technical data.
simple cable length (L*)
A = cable cross-section
I = sum of the rated drive current draws
*L = simple line length
73 = factor, made up from 2.5 V max. permissible voltage drop and
electrical conductivity of copper
Notes re-selection of cables
For the motor supply cables of SHE drives 3 or 5 (duplicated layout) individual cores are required.
Two cores (4 cores) are for the motor voltage, the 3rd or 5th core respectively is required for monitoring the cabling.
The selection and layout of the cables is to be performed according to (model) utility facilities guidelines (MLAR). Here
particular attention is to be paid to E30 or E90 functionality retention!
Examples of cable types and fittings that can be used
E30 / E90 cable
yellow-green: cannot be used for the cabling monitoring
Cable system, consisting of load support system and cables with appropriate fire protection tested wall
plugs and screws. Cable system in accordance with DIN 4102-12 Safety cable + layout system
Cabling example
junction box
Motor
brown
M
blue
=
Motor voltage
Cabling monitoring