SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
Description of function
Automatic ventilation control
If activated (see start up procedure), the windows are closing automatically after xx min (10 min factory-made), in case of
mains or battery failure, the windows close immediately.
See also page 63, DIP-Switch
Mains or battery failure
- Automatic closing of the flaps
- Ventilation function locked, SHE function active
Note: These are standard features for mains or battery failure,
Special function: see DIP switch function 3 + 10
Extraction limit (by operating time)
See note on page 62, switch DIP-Switch 6 to ON.
Teaching
Close the windows. Earliest start of the learning mode after 30 seconds. Press the switches "Open" and "Closed" (STOP)
at the vent switch as long as the display "Open" is flashing fast. Open the motor with the switch "Open" up to the position
required within the next 10 sec. and stop the motor in this position by releasing the switch "Open".
If no other switch is pressed within the next 10 sec. the learning phase is finished.
To deactivate
See note on page 58, switch DIP-Switch 6 to OFF.
Note: If the vent switch has no Open-display or there is no ventilation button in the door of the TRZ-Plus
Comfort the stroke limit setting must be made through the optional service port software.
Note: In case of mains or battery failure or SHE activation the function is out of order. In case of mains or
battery failure, the windows close immediately.
LED display
In the SHE control panel and SHE manual call points.
The green LED display
- mains or battery failure
- malfunction of the line monitoring of the connected drives, automatic detectors or SHE manual call points.
The yellow LED display
battery failure.
Caution: If any malfunction is indicated the malfunction has to be eliminated immediately. The perfect function
of the system is no longer guaranteed.
The red LED display
Closing with wind/rain detector
If a wind/rain detector or a rain sensor is connected, the windows close automatically in case of beginning winds and/or
rainfall, "Ventilation Open" display flashes, vent switch out of order. The windows close immediately in case of power or
battery failure.
Note: The ventilation function is out of order or locked in case of power or battery failure or SHE activation in
order to save battery power.
46
12.
- operating OK - is shining. It goes out in case of:
OK
- malfunction - is flashing in case of: malfunction, cable connection defective, mains and/or
- SHE activation - is shining in case of: manual or automatic SHE activation.