Function of DIP-Switches

Adjustable functions for ON setting
DIP-Switch 1: Motor timing device is switched off (VdS function)
DIP-Switch 2: Motor output permanently switched on
DIP-Switch 3: Central control system door locking function with magnetic clamps or
magnetic latches
DIP-Switch 3 + 9: Voltage source 27 V DC / 100 mA *
DIP-Switch 4: "Fire Alarm System Open" and "Reset via 1 x Fire Alarm System closer contact"
DIP-Switch 5: Pre-alert
DIP-Switch 6: Actuation limit
DIP-Switch 7: Malfunction = SHE activation
DIP-Switch 7 + 3: Malfunction = Ventilation on *
DIP-Switch 8: SHE Closed (on the SHE operating station) = SHE-Reset
DIP-Switch 9: Ventilation in inching mode of operation (deadman button)
DIP-Switch 10: STOP function with key-operated ventilation button
DIP-Switch 11: Detector monitoring with 10KΩ Monitoring resistor
DIP-Switch 12: Automatic closure system, automatic closure
Combinations of various DIP-Switch settings are possible, e.g. DIP-Switch 1 = ON and 8 = ON.
DIP-Switches
Attention: All settings of the DIP-Switches have to be made without current (230 V AC) and without
accumulator attached.
Factory settings for the DIP-Switch are position OFF. Position ON, means:
DIP-Switch 1: Motor timing device is switched off (in SHE for 30 min, VdS function).
DIP-Switch 2: Motor output permanently switched on for operation with magnetic clamps to reinforce the locking force
of the drives (sealed closure of windows). Battery is not buffered. Switched off in the factory, thus motor outputs are
switched off after approx. 3 min.
DIP-Switch 3: Function of the control panel to secure the door with magnetic clamps and on site provided door closer or
SHE-Open with magnetic lockets with on site provided gas springs. At the motor exit is permanent voltage, this will be
switched off in case of SHE.
DIP-Switch 3 + 9: Voltage source 27 V DC / 100 mA *
Switching the function "output horn / signal light" at the terminals 20 and 21 on the function „27 V DC / 100 mA voltage
source". This voltage is permanently available, but is not battery-backed.
At 230 V voltage failure this output also switches off.
This output is used for power supply of sensors, such as a multisensor for CO
ON
1 2 3 4 5 6 7 8 9
10 11 12
* from Firmware > V01.00.11
13/24999513
SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
DIP-Switches