SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
Possible connections
- linear drives 24 V DC with integrated electronic power cut-off, tandem power cut-off, synchro module or
chain motors 24 V DC with limit switches
- overall power consumption of all motors connected max. 2 A
- 10 SHE manual call points RBH/3A... (line termination via enclosed end resistance)
- 10 automatic detectors with 2-wire-technology, optical smoke detectors and/or detectors of heat differential and/or
detectors of maximum heat or monotoring resistor ex factory via the final fuse attached
- 10 external ventilation switches "Open/Stop/Closed" (e.g. type LTA 25)
- 24 V DC siren or flashing lights, max 100 mA
- to connect 1 wind-/rain detector (e.g. type WRM 24V, WRM2) or 1 rain detector (e.g. RM, RM2)
Only with TRZ Plus Comfort or with additional module WRMAS.
- in each case one connection for potential-free report SHE activated (NO= normally Open contact) and malfunction
(NC= normally closed contact): 24V / max. 0.5 A
Only with TRZ Plus Comfort or with additional module WRMAS.
Fuse
F1 mains
Additional modules connection
The extension by the additional module TRZ/WRMAS* and TRZ RBH* are an option, it is not part of the standard
supply. Please ask your distributor if required.
1. Wind-rain-detection-alarm-malfunction (TRZ/WRMAS-Basic)
The following components can be connected:
1 x connection wind/rain detector or rain detector
1 x pot.-free transmission Alarm (SHE-activation), Closing contact max. 30 V DC / 0.5 A
1 x pot.-free transmission collect. malfunction, Opening contact max. 30 V / 0.5 A
Opening contact collective malfunction
Closing contact alarm (SHE)
* standard included in the TRZ Comfort Plus
48
F2 Motor
F3 battery
LED display
Fuse
Extension ledge
Switch "SHE Closed" Reset
Extension ledge
DIP-Switch
PC Service Port
Fuse battery
Battery connection