SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
Possible connections
Installation
Disconnect the control panel from power supply (mains and battery), plug the spacer to the principal circuit control board,
plug the additional module to the extension ledge, create the desired connections and check, re-establish power supply
(mains and battery).
Check wind/rain detection function
No SHE and no malfunction signal, the green LED
operating is shining. Press the switch Open at the vent switch, the
OK
motor opens. Moisten the rain sensor surface of the weather detector, the drives close. If the vent switch has a
display for Open, it flashes. The ventilation function is blocked as long as a wind or rain alarm is pending. Activate
SHE
- the drives have to open during a pending wind or rain alarm (SHE has priority). To test the wind detection, a
permanent air current has to be detected at the wind wheel approx. 3 min (e.g. a hair dryer). Otherwise proceed for the
checking as described above.
Check Alarm (SHE) and malfunction function
No SHE and no malfunction detection, green LED
- operating - is shining. Activate SHE
. The closing contact at
OK
the terminals 4 + 5 switches. The function is OK if the passage can be measured. Activate SHE Closed
, initial
position, no SHE-activation and no malfunction detection. Take off the battery fuse F3 to simulate a malfunction,
Activation! Replace fuse F3 back, control panel again in initial position, repeat complete bringing into service of the
TRZ Plus 2A. No errors, function is OK, system ready for operation.
2. SHE manual call point TRZ/RBH-Basic
integrated in the TRZ Plus front door. Not suitable for compact control panel 2A and 2A/M.
LED-display
Extension ledge
Switch SHE-activation
Switch SHE Closed (no Reset)
SHE manual call point TRZ/RBH
Installation
Disconnect power supply (mains and battery), mount additional module at the inside of the control panel door, plug the
plug to the extension ledge of the principal circuit control board or, if available, of the add. module TRZ/WRMAS,
reconnect power supply (mains and battery).
Function check
Proceed as indicated page 65, point "SHE man. call points", repeat the complete bringing into service of the TRZ Plus,
no errors, function OK, system is ready for operation.