Start up procedure and trial run
SHE manual call points
Press SHE Open switch briefly, the windows open completely. The red LED display
The green display
- Operation OK - lights up. The continuous acoustical signal sounds (only by SHE man. call point
OK
with buzzer and if the door contact switch is pressed). Press switch Closed in the vent switch, no drive reaction.
Press Reset switch in the control panel, the windows close completely. The red LED display
out. The green LED display
Press SHE Open briefly, the windows open. During running, press the Open and Closed switches in the vent switch at
the same time. No reaction at the windows, they must not stop.
Press the SHE-Reset switch in the control panel, the windows close completely.
Test emergency power supply
Disconnect mains power supply, the green LED
The yellow LED
- malfunction -flashes. In case of power failure, the windows close immediately.
Press the "Open" switch of the vent switch, no window reaction.
Press the switch SHE "Open", the windows open.
The red LED
- SHE activation - is shining.
The green LED
"operating OK" not lit up.
OK
Press the switch "Closed" of the SHE manual call point, the windows close completely.
The red LED
"SHE-activation" goes out. The yellow LED
Re-connect mains voltage, the green LED
Test automatic detectors
Trigger the automatic detector (e.g. with test spray): the red LED in the autom. detector is shining.
The red LED
"SHE activation" is shining.
The green LED
"operating OK" is shining.
OK
The windows open completely.
Press the switch "Closed" of the vent switch, no window reaction. Get rid of the smoke in the detectors, otherwise
reactivation may occur.
Press the switch "SHE-Reset" in the control panel, the windows close completely and the automatic detector is Reset.
The red detector LED goes out.
Test automatic ventilation control
(DIP-Switch 12 to ON)
Press Open switch in the vent switch, the windows open completely. The windows close again automatically after
10 minutes.
13/24999513
SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
- Operation OK- lights up. The continuous acoustical signal stops.
OK
"operating OK" goes out (after max. 100 sec).
OK
"operating OK" is shining after a moment. Reset the activation.
OK
- SHE activated - lights up.
"malfunction" flashes.
- SHE activated - goes