Possible functions, digital input/output 4
Function if input
See details in section

17.13 Digital inputs

• Not active
• External stop
• Min.
• Max.
• "User-defined speed"
• External fault
• Alarm resetting
• Dry running
• Accumulated flow*
• "Predefined setpoint digit
3"
• "Activate output"
• "Local motor stop"

17.15 Activation delay

Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Select the activation delay, T1.
It is the time between the digital signal and the activation of the
selected function.
Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 58.
Not active
active with interrupt, mode A
active without interrupt, mode B
active with after-run, mode C.
Select the duration time, T2.
It is the time which, together with the mode, determines how long
the selected function is active.
Range: 0 to 15,000 seconds.
T input > T1 + T2
T input > T1 + T2
Digital input
T input
Mode A
T1
T2
Mode B
T1
T2
Mode C
T1
Fig. 58 Duration timer function of digital inputs
Factory setting
See section
35. Factory
settings.
42
Function if output
See details in section
17.16 "Signal relay 1 and 2"
(Relay outputs)
• Not active
• Ready
• Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
• Digital input 1, state
• Digital input 2, state
• Digital input 3, state
• Digital input 4, state
Activation delay
-
T input < T1 + T2
T input < T1 + T2
T input
T1
T1
T2
T2
T1
T2

17.16 "Signal relay 1 and 2" (Relay outputs)

Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Function
Relay output 1
Relay output 2
* See section
9.5.1 Connection terminals, advanced functional
module, FM
300.
The pump incorporates two signal relays for potential-free
signalling. For further information, see section
Function
You can configure the signal relays to be activated by one of the
following incidents:
Not active.
Ready
The pump can be running or is ready to run and no alarms are
present.
Alarm
There is an active alarm and the pump is stopped.
"Operating" (Operation)
"Operating" equals "Running" but the pump is still in operation
when it has been stopped due to a warning.
"Running" (Pump running)
Warning
There is an active warning.
Digital input 1, state
Follows digital input 1. If digital input 1 is activated, output is
also activated.
Digital input 2, state
Follows digital input 2. If digital input 2 is activated, output is
also activated.
Digital input 3, state
Follows digital input 3. If digital input 3 is activated, output is
also activated.
Digital input 4, state
Follows digital input 4. If digital input 4 is activated, output is
also activated.
Limit 1 exceeded
When the Limit 1 exceeded function is activated, the signal
relay is activated. See section
Limit 2 exceeded
When the Limit 2 exceeded function is activated, the signal
relay is activated. See section
Relubricate
External fan control (Control of external fan)
When you select "External fan control", the relay is activated if
the internal temperature of the motor electronics reach a
preset limit value.
Factory setting
See section
35. Factory
settings.
"Signal relays 1 and 2"
Terminal*
NC, C1, NO
NC, C2, NO
22. Signal
relays.
17.23 Limit-exceeded
function.
17.23 Limit-exceeded
function.