ELECTRICAL INSTALLATION
Wiring Guidelines
Maximum Motor Cable Length
Motor
Motor Family
Voltage
214 505 xxxx
230
214 507 xxxx
230
214 508 xxxx
230
224 300 xxxx
230
224 301 xxxx
230
234 511 xxxx
230
234 512 xxxx
230
234 513 xxxx
230
234 514 xxxx
230
234 515 xxxx
230
1
Based on a 5% voltage drop with 1000 ft limit.
Notes:
•
The use of 600 V minimum rated motor cable is required.
•
Maximum allowable wire lengths are measured between the controller and motor, based on AIM Manual
requirements with up to 1000 ft limit. Larger wire and filtering are required if exceeding the 1000 ft limit.
•
Flat-jacketed submersible motor cable is recommended. All splices in the motor cable must be properly
sealed with watertight shrink tubing. Use extreme caution to avoid damaging or compromising the
motor cable insulation during installation or service.
Conduit Locations and Sizing
Use appropriate strain relief or conduit connectors.
1.
Incoming power supply—Hole = 0.88 in. (22.2 mm)
2. Power output to motor—Hole = 0.88 in (22.2 mm), Knockout = 1.11 in. (28.2 mm)
3. Control wiring (sensor) input—Hole = 0.5 in. (12.7 mm)
18
Phase
Horsepower
1
1/2 (0.37 kW)
1
3/4 (0.55 kW)
1
1.0 (0.75 kW)
1
1.5 (1.1 kW)
1
2.0 (1.5 kW)
3
1/2 (0.37 kW)
3
3/4 (0.55 kW)
3
1.0 (0.75 kW)
3
1.5 (1.1 kW)
3
2.0 (1.5 kW)
AWG 600V Copper Wire Sizes, 75° C Insulation, and
Motor Cable Lengths (in feet)
14
12
10
400
650
1000
300
480
760
250
400
630
190
310
480
150
250
390
930
1000
1000
670
1000
1000
560
910
1000
420
670
1000
320
510
810
1
8
6
4
1000
1000
1000
1000
1000
1000
990
1000
1000
770
1000
1000
620
970
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000