Electrical Connection; Installation Accessories - Burkert 2000 Mode D'emploi

Masquer les pouces Voir aussi pour 2000:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

11 ELECTRICAL CONNECTION
Image 13: Connection of the device socket
Loosen the cheese head screw (3) on the device socket and
remove it.
NOTE!
Functional failure due to bent connector lugs that prevent the
contact insert from being reinstalled.
▶ Carefully remove the contact insert and ensure that the connector
lugs are not bent.
Loosen the hollow screw in the contact insert (2), remove the
contact insert from the cap.
Guide the cable through the union nut (8).
22
Item Parts designation
1
Flange seal
2
Contact insert
3
Cheese head screw
4
Cap
5
Thrust collar
6
Sealing ring
7
Collet chuck
8
Union nut
English
Type 2000, 2006, 2012
Electricalconnection
Make the connection according to the circuit (see "Image 14:
Electrical circuit").
Max. connected loads: 5 A at 250 VAC
0.25 A at 250 VDC.
Image 14: Electrical circuit
Insert the contact insert (2) into the cap (4) and screw on with a
hollow screw.
Screw on the device socket with the cheese head screw (3)
(tightening torque 0.5 Nm or hand-tight), making sure that the
flat seal (6) is seated securely.
Tighten the union nut by hand.
Check valve for functionality and tightness.
12 INSTALLATION ACCESSORIES
Product
Actuator size [ø in mm]
Special wrench
2030, 2031, 2032, 2033
Assignment: 1. Input
2. Normally
closed contact
3. Normally
open contact
Order no.
50
639 175
63
639 170
80
639 171
100
639 172
125
639 173

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

200620122030203120322033

Table des Matières