Settings

GB
4. Settings

4.1 Use of an external controller

18
When using external controllers for actuation of the individual boiler, eg., with the
aid of the 0-10V performance requirement or a consumer circuit requirements, the
boiler to be connected may only be switched on if the boiler that is operating has
reached approx. 30% of maximum capacity. Here the following values must be set
if needed under Prog.-no. 9524:
Boiler
SGB 400 E
SGB 470 E
SGB 540 E
SGB 610 E
Flue cascade system BK 350
Setting prog. no. 9524
129 kW
148 kW
148 kW
169 kW
7308114-01 04.13