INSTAllATION CONFIGUrATION: A FEW EXAMPlES
h, l: minimum 2''
In all possible configurations, it is essential to comply with the minimum sizes
for each of the three air flows (combustion, convection and ventilation).
minimum size*
Combustion
18.6 in
2
/ 120 cm²
2
Convection
93 in
/ 600 cm²
2
Ventilation
62 in
/ 400 cm²
When the air in the room is used for combustion, it is recommended that sepa-
rate entries be used and the combustion air channelled (flexible or PVC pipe) to
ensure that the ventilation does not interfere with combustion.
Insulating panel
Insulating panel
H
qUElqUES EXEMPlES DE CONFIGUrATIONS POSSIBlES
Panneau d'isolation
H
Panneau d'isolation
H
Dans toutes les configurations possibles, il est essentiel de respecter les tailles mini-
males pour chacun des trois flux d'air (combustion, convection et décompression).
taille minimum*
2
Combustion
120cm²/ 18.75 in
Convection
600cm²/ 93 in
2
Décompression
400cm²/ 62 in
2
en cas d'utilisation d'air de la pièce pour la combustion, il est conseillé de prévoir des
entrées séparées et de canaliser l'air de combustion (flexible ou tuyaux pvc), pour
éviter que la ventilation interfère avec la combustion.
h, l: minimum 5 cm
23