16. ERROR CONDITION AND RESET

Display
indication
e0 – e16
e37
e38
24
Description
Reset
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
Internal error
again.
- If the error persists, change the circu-
lator.
- Switch off system power.
- Wait for the warning lights on the control
Low mains
panel to go off, then power the system
voltage (LP)
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Switch off system power.
- Wait for the warning lights on the control
High mains
panel to go off, then power the system
voltage (HP)
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
Critical
overheating of
e32-e35
electronic parts
Protection
e39-e40
v
against
overcurrent
e21-e30
Voltage Error
Twin
communication
e31
v
absent
e42
Dry operation
Motor excess
e56
temperature
f < 100 Hz
e57 ; e58
f > 5 kHz
- Switch off system power.
- Wait for the warning lights on the control
panel to go off.
- Check that the system ventilation
ducts are not blocked and that the en-
vironment temperature of the premises
is correct.
- Check that the circulator turns freely.
- Check that any antifreeze added does
not exceed the maximum percentage
of 30%..
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Check that the twin communication ca-
ble is intact.
- Check that both circulators are powe-
red.
- Put the system under pressure.
- Switch off system power.
- Wait for the motor to cool down
- Power the system again
Check that the PWM external signal is