Pumped Liquids; Applications; Technical Data - DAB EVOplus + small 40/180 M Manuel D'installation

Masquer les pouces Voir aussi pour EVOplus + small 40/180 M:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 51

3. PUMPED LIQUIDS

The machine has been designed and made for pumping water, free from
Kg/m³, a kinematic viscosity of 1mm²/s and non chemically aggressive
liquids. It is possible to use ethylene glycol in a percentage of no more
than 30%.

4. APPLICATIONS

EVOPLUS SMALL series circulators allow integrated adjustment of
the differential pressure which enables the circulator performance to be
adapted to the actual requirements of the system. This determines con-
siderable energy saving, a greater possibility of control of the system,
and reduced noise.
EVOPLUS SMALL circulators are designed for the circulation of:
- water in heating and conditioning systems.
- water in industrial water circuits.
- domestic water only for the versions with bronze pump body.
EVOPLUS SMALL circulators are self-protected against:
- Overloads
- Lack of phase
- Excess temperature
- Over-voltage and under-voltage

5. TECHNICAL DATA

Supply voltage
Absorbed power
Maximum current
Grade of protection
Protection class
TF Class
Motor protector
Maximum environment temperature
Liquid temperature
Flow rate
Head
Maximum working pressure
Minimum working pressure
Lpa [dB(A)]
ENGLISH
1x220-240 V (+/-10%), 50/60 Hz
See electrical data plate
See electrical data plate
IP44
F
TF 110
No external motor protector is
needed
40 ºC
-10 ºC ÷ 110 ºC
See Table 1
See Table 1
1.6 MPa
0.1 MPa
<= 33
GB
15

Publicité

Table des Matières
loading

Table des Matières