2-8. Electrical Service Guide

60 Hertz Models
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length
In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1993 National Electrical Code (NEC)
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1993 National Electrical Code (NEC)
With Power Factor Correction
200
(208)
78
125
8
61 (19)
8
50 Hertz Models
230
460
575
68
34
27
100
50
40
8
12
14
131
133
80 (25)
(40)
(40)
8
12
14
Without Power Factor Correction
220
84
125
8
76 (23)
8
Without Power Factor Correction
200
230
460
(208)
103
90
45
150
125
70
6
8
10
208
87 (27)
77 (23)
(64)
6
8
10
380
49
70
10
153 (47)
205 (63)
10
OM-321 Page 13
575
36
50
12
200
(61)
12
S-0092-J
440
42
60
10
10
S-0092-J