4-11. Remote Amperage Control Receptacle

2

4-12. Electrical Service Guide

Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Normal Operating
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2005 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
1
1
2
Time-Delay
3
4
4
1
Remote Amperage Control
Receptacle RC1
2
Keyway
To connect remote amperage con-
trol to receptacle, insert plug and
turn clockwise until tight.
208
230
460
89
80
40
110
100
50
125
125
60
4
6
8
171
142
375
(52)
(43)
(114)
6
6
10
Ref. 802 927
575
32
40
50
10
395
(120)
10
OM-2230 Page 17