This involves determining a differential pressure
and saving a pressure loss characteristics curve
for every volumetric flow (HPV, RV, NV, IV) with
clean filters.
The `Permissible delta p´ parameter specifies the
maximum permissible increase in pressure in %.
Before activating filter monitoring, be sure
to insert new air filters in the ventilation unit.
If the `Filter monitoring´ parameter is set to
yes, the ventilation unit is set to the current
pressure loss – the unit runs through the entire
volumetric flow range from RV to IV for 10
minutes.
This initialisation sequence takes place whenever
a filter change is acknowledged.
For additional information about filter monitoring
→ accessories instructions.
9.14 EnOcean wireless (E-SM plug-in
module)
Parameters: EnOcean wireless
Set value: no / yes
Parameters: Learning mode
Set value: inactive / active
Parameters: Unit list
Set value: inactive / active
Parameters: Unlearn units
Set value: Here you can either unlearn all or just
individual EnOcean wireless units.
For additional information about the EnOcean
wireless plug-in module E-SM → EnOcean/KNX
plug-in modules [} 56] or accessories instruc-
tions.
9.15 KNX (plug-in module K-SM)
Parameters: KNX
Set value: no / yes
For additional information about the KNX plug-in
module K-SM → EnOcean/KNX plug-in modules
[} 56] accessories instructions.
9.16 BACnet
For further parameters → BACnet description of
parameters. This can be downloaded from the
service area at www.maico-ventilatoren.com.
9.17 Switching test
Parameters: Supply air fan
Set value: Off / On
Parameters: Exhaust air fan
Set value: Off / On
Parameters: Bypass shutter
Set value: Open / Closed
Parameters: Preheating register
Set value: Off / On
Parameters: Switching contact Basic circuit
board (main circuit board)
Set value: Off / On
Parameters: Brine circulating pump (ZP 1)
Set value: Off / On
Parameters: Zone shutter, zone 1 (ZP 1)
Set value: Left / Centre
Parameters: Zone shutter, zone 2 (ZP 1)
Set value: Right / Centre
Parameters: 3-way air shutter (ZP 1)
Set value: Off / On
Parameters: Supplementary heating relay (ZP 1)
Set value: Off / On
9.18 Internet
Parameters: IP address configuration
Set value: Static / Dynamic DHCP (factory set-
ting)
Parameters: IP address
Set value: dynamic
Parameters: Subnet mask
Set value: dynamic
Parameters: Gateway
Set value: —
Parameters: DNS
Set value: —
Parameter: air@home
Parameters: No / Yes
Parameters: Web server reset login
Set value: reset / do not reset
9 Unit settings menu
49