9 Unit settings menu
The filter service life is reset. With the RLS 1 WR
single control unit, the filter change interval is in-
dicated by the central LED flashing. This is reset
by pressing the two arrow keys at the same time
for approx. 5 sec.
9.3.7 External filter
Parameters: External filter
Set value: No / Yes
Parameters: Filter service life, external filter
Set value: 3 ... 6 ... 18 months
Parameters: Filter change, external filter
Set value: No / Yes
External filter yes activates the filter change indic-
ator for an outside air filter upstream of the ventil-
ation unit.
If the filter is changed prematurely, the filter
change must be confirmed. This is done by se-
lecting yes under `Filter change´ `External filter´.
The filter service life is reset.
9.3.8 Room filter
Parameters: Room filter
Set value: No / Yes
Parameters: Filter service life, room filter
Set value: 1 ... 2 ... 6 months
Parameters: Filter change, room filter
Set value: No / Yes
Room filter yes activates the filter change indic-
ator for the room filters in the air inlets, e.g. for ex-
haust air filter elements. If the filter is changed
prematurely, the filter change must be confirmed.
This is done by selecting yes under `Filter change
´ `Room filter´. The filter service life is reset.
9.3.9 Duration of ventilation level
Parameters: Duration of ventilation level (pause
ventilation)
Set value: 1 ... 30 ... 120 min
Operating time of a manually selected ventilation
level in Auto sensor or Auto time operating mode
or intermittent ventilation.
9.3.10 Motion detector overrun time
Set value: 5 ... 12 ... 120 min
Duration of unit operation after room use is last
detected by motion detector.
Comments: If units are fitted with motion detect-
ors, unit operation is only activated once room
use is registered (motion detected).
Exception: AutoTime operating mode.
Motion detector is only active if it was set/activ-
ated within the time program. If unit operation is
activated by the motion detector, the unit is al-
42
ways operated in a demand-driven manner based
on the measurements of connected sensors
(CO2, VOC).

9.4 Ventilation time programme

Control time program/holiday time program
The time programs are activated by the Auto time
operating mode. The control time program is al-
ways activated. The holiday time program can be
activated with time limits by specifying a time
range using the 'Start date for holiday time pro-
gram' and 'End date for holiday time program'
parameters. The 'Holiday time program active'
note is present for the duration of the activated
holiday time program.
Parameters: Start holiday time
Set value: Date entry
Parameters: End holiday time
Set value: Date entry
You can program a daily time program with 6 time
windows and assigned ventilation level/function
for every day of the week. The daily time pro-
grams can be programmed individually. Alternat-
ively, they can be programmed for several days
by activating the desired days of the week. Indi-
vidual days can also be copied later on. The vent-
ilation level/function activated by the daily time
program remains active until it is replaced by an-
other air level/function starting within the time pro-
gram.
Setting options for `Control time program´/
`Holiday time program´