9 Unit settings menu
● Exhaust air temperature sensor tolerance too
high.
This parameter can be used to adjust the actual
room temperature. The adjustment is based on
the room sensor selected under room sensor con-
figuration .
Example: Actual room temperature measured on
comfort control unit 20.3 °C. With Room temper-
ature adjustment of -0.4 K, an actual room tem-
perature of 19.9 °C is displayed.

9.5.2 T supply air min. cooling

Parameters: T supply air min. cooling
Set value: 8 ... 14 ... 29°C
Limits the minimum supply air temperature if cool-
ing with bypass. Bypass sometimes closes if the
set temperature is not being met. The ventilation
unit regulates the supply air temperature to the
set value.
9.5.3 Maximum room temperature
The minimum temperature difference
between the parameter `Room setpoint tem-
perature´ and the maximum room temperat-
ure is 2 °C. If the temperature falls below the
permissible temperature difference, an auto-
matic correction is made.
Parameters: Maximum room temperature
Set value: 18 ... 24 ... 30°C
The control releases cooling via the bypass when
the set maximum room temperature is reached
(measurement on temperature sensor).
Conditions for cooling via the bypass
● T outside air > 5° C with single control unit in
solo mode
and
●T outside air < T room reference and T room
reference > maximum room temperature
9.5.4 Room setpoint temperature
Parameters: Room setpoint temperature
Set value: 18 ... 23 ... 25°C

9.6 Sensors

Combi sensor operation

Adjustment of humidity combi sensor/temperature
combi sensor
Sensor 1 configuration:

Sensor 1

Sensor 1 type
Sensor 1 name
Sensor 2 configuration:
Sensor 2
44
Sensor 2 type
Sensor 2 name
Sensor 2 digital function
Sensor selection Sensor 3 and 4 configuration
active, if parameter `Single control unit´ switched
inactive
CO2 limit value min.
CO2 limit value max.
VOC limit value min.
VOC limit value max.
Rel. min. humidity limit
Rel. max. humidity limit

Rel. humidity control voltage 0 V

Rel. humidity control voltage 10 V
CO2 value control voltage 0 V
CO2 value control voltage 10 V
VOC value control voltage 0 V
VOC value control voltage 10 V
9.6.1 Combi sensor operation
Parameters: Combi sensor operation
Set value: stepped / linear
Stepped: Rel. humidity value limit max. for in-
tensive ventilation. The maximum value always
serves as the switching point for dehumidification
in the Auto Time and Auto Sensor operating
modes. The minimum value is not taken into ac-
count.
Linear: Rel. humidity limit min/max for intensive
ventilation with linear humidity control in Auto
Sensor operating mode. The maximum value al-
ways serves as the switching point for dehu-
midification in the Auto Time and Auto Sensor
operating modes. The minimum limit value ap-
plies to reduced ventilation. Between RV and IV,
regulation is linear, stepless and demand-based.
Setting also applies to nominal ventilation
for single control unit in solo mode and linear
setting. The limit value settings apply to the
humidity value (optional).
For sensor limit value settings → Chapter 9.6.5,

CO2-/VOC-/Rel. Humidity limit value min./max.

[} 45].
9.6.2 Combi sensor humidity adjustment /
Combi sensor temperature adjustment
Parameters: Humidity adjustment Combi sensor
Set value: -15 ... 0 ... 15 %
Parameters: Temperature adjustment Combi
sensor
Set value: -3 ... 0 ... 3°C
Corrects any deviations which may arise in the
combi sensor humidity/temperature value.