9 Unit settings menu
9 Unit settings menu
Basic settings can be configured in the Unit set-
tings menu. Depending on authorisation (user),
different unit parameters can be set.
9.1 Operating structure for unit set-
tings
Basic settings
Ventilation
Ventilation time programme
Temperatures
Sensors
Fireplace
Brine EHE
Zone ventilation
3-way air shutter
Supplementary heating
Pressure consistency
Filter monitoring
EnOcean wireless
KNX
Switching test
Internet
38
NOTICE Incorrect settings can cause faults
and malfunctions.
Settings can only be undertaken in the installer
level by authorized trained specialists in ventila-
tion technology.
To activate the installer level, go to "Installer"
field and enter the password 6940.
9.2 Basic settings
Single control unit lock
Room sensor configuration
Single control unit: RLS 1 WR control unit
Single control unit: Blocking off
Switching contact function
Bypass
Preheating register
Heat exchanger type
Acknowledgement of external safety device
Factory settings for control
9.2.1 Single control unit lock
Single control unit = RLS 1 WR
Single control units can be locked from a main
control unit. All single control units are then deac-
tivated.
Parameters: Control unit locks
Set value:
Inactive: All single control units are enabled.
Active: All single control units are deactivated.
9.2.2 Room sensor configuration
Parameters: Room sensor configuration
Set value: External, internal, bus, control unit
The temperature determined with the selected
room sensor is used as the room temperature to
control the bypass and any supplementary heat-
ing connected.
9.2.3 Single control unit: RLS 1 WR control unit
Solo mode only possible if no RLS T2 WS is con-
nected. Function not available with AIR@home
APP or AIR@home web tool.
Parameters: Single control unit: RLS 1 WR con-
trol unit
Set value: Solo, Auxiliary, Inactive/sensor, Di-
gital/building control system
Solo: Ventilation unit is operated with supplied
RLS 1 WR single control unit + maximum of 4 op-
tional single control units.
Auxiliary: Ventilation unit is operated with one op-
tional RLS T2 WS comfort control unit + max-
imum of 5 optional single control units.