YES
WEB page is reachable, but the browser is unable to load it. Open a TELNET ses-
sion:
Telnet < ip address> 10000
Password : gtmt
Proceed to a "Factory Default", then "Quit and save". Refresh the WEB page.
aN OUTPUT IS NOT vISIBLE IN ThE CONfIGURaTION WEB PaGE ?
►
Press 'F5' to refresh the WEB page, and go back to output panel. If the output is still
missing, see next point.
►
Open a TELNET session:
Telnet < ip address> 10000
Password : gtmt
Proceed to a "Factory Default", then "Quit and save". Refresh the WEB page.
►
If the output is still missing, open the device. Check the black cables connections
and the switches configurations (see Appendix D – MAINTENANCE / Output card
switches verification).
THE SCREEN DISPLAYS "NO TIME CODE!" OR "NO TIME CODE!" ?
►
"NO TIME CODE!" : verify your time source because the device is not synchronized.
►
"no time code!" with the date : if your device receives time code, verify in the input
panel of the configuration WEB page that "run autonomous" is not checked.