Mains present: indicated remotely by dry contact (failsafe).
If there is no mains power > orange LED + message on display: "Mains fault".
Charger present: indicated remotely by dry contact (failsafe) with time delay.
If the mains fuse is blown or not present.
If mains is < 98V.
If the product is out of order.
Battery present: indicated remotely by dry contact (failsafe) with time delay.
If the battery is not present:
The battery test is performed as follows: every 30 seconds during the first 20 minutes after
commissioning: every 15min after the first 20 minutes. If a fault is detected, the test is
performed again every 30 seconds up to 20 minutes after the fault disappears.
Indicated locally by orange LED + display message: "Battery fault"
If the battery voltage < 1.85 V/cell ±3 %, indicated locally by an orange LED + display message:
"Battery fault".

6.2 Available equipment and options

Battery low voltage cut-out:
The cut-out threshold is 1.8 V/cell
The element causing the outage will be in the + position.
Battery current limitation:
The charge current is controlled and electronically limited to 75 % of In.
Battery current limitation option:
The battery charge current can be set to 25 %, 50 %, 75 % of the rated current (In) using a configuration jumper
on daughterboard positions '25', '50', '75'.
±3 %.
Daughterboard
Daughterboard jumper
58