7.3 Display operation
7.3.1 Information display
On the display
•
Battery voltage and current: The information displayed is e.g.:
"Ubat = 24V I = 20A".
•
Load voltage (by load output if possible). Voltages Load1 and Load2 are displayed but not
the current per output because this information is not available. The information displayed is,
e.g. for Load1 and Load2: "U1 = 24V U2 = 24V".
•
Total current of the load outputs: The current consumed by the load outputs is deduced from
the total charger current of the and the battery current. The information displayed is e.g.: "I = 20
A".
•
information about the various problems (mains, charger, fuse, battery, etc.) Malfunctions
are indicated by the colour of the LED and the text displayed permanently on the screen:
▪
▪
▪
▪
▪
▪
▪
The display has a standby mode controlled by the IP board. This mode helps save energy and prolong its life.
To exit standby mode, press the button on the front of the rack.
The LED
A two-colour operating state LED completes the display:
-
-
Briefly pressing the front panel button scrolls the information on display. If the button is not pressed, the
information automatically changes every minute. Once the end of the list has been reached, the information
begins to scroll again from the beginning.
If the button is held down longer than 10s, the display shows the IP address of the rack. This display
disappears after a minute or if the button is pressed shortly.
If no action is taken for 15 minutes, the display will return to standby.
7.3.2 Fault text messages
Screen display
Fuse AUX fault
Battery fault
Back up fault
Mains fault
Charger fault
Fuse 8 fault
Fuse 7 fault
Battery fault
Back-up fault
Mains fault
Charger fault
Fuse 8 fault
Fuse 7 fault
AUX fuse fault (3 – 4 – 5)
Green: everything is OK, normal operation.
Orange: A fault is present.
Explanation
One of the output fuses 3, 4, 5 is out of order
Battery absent or too low, or the voltage is too high
The battery is nearly empty (a power cut is imminent)
No mains voltage
The AC/DC converter has failed
The load1 output fuse is out of order
The load2 output fuse is out of order
180140005Ca
Code: