2 SPECIFICATION
2.4 Technical Data
General Data
Pipe diameter
Measuring range
Flow range
Flow range
Plastic fitting
Pressure class
Fluid temperature max
Metal fitting
Pressure class
Fluid temperature max:
Ambiant temperature
Storage temperature
Relative humidity
Enclosure
Measuring error
Linearity
Repeatability
Pulses/rotation
Fitting
Paddle-wheel
O-rings
Housing
Specific data SE30
Only for use with battery powered flow transmitter type 8025 or indicator type SE34
Measuring range
Power Supply
Output signal
Cable L. max.:
Specific data SE30
Measuring range
Power Supply
Output signal
Cable L. max.:
Specific data SE30
Measuring range
Cable L. max.:
Can only be connected to Burkert devices
8030
from DN 15 to DN 50 (1" to 2")
0.3 to 10 m/s (1.0 to 32.8 fps)
as from 3 l/min (DN15 pipe, 0.3 m/s flow velocity)
as from 1.0 gpm (1/2" pipe, 1.0 fps flow velocity)
PVC; PP; PVDF
PN10
PVC: 50 °C (132 °F); PP: 80 °C (176 °F); PVDF: 100 °C (212 °F)
Stainless-stel (316L/1.4404); brass (Cu Zn39 Pb2/DIN 17400)
PN16
100 °C (212 °F)
0 to 60 °C (32 to 140 °F)
0 to 60 °C (32 to 140 °F)
max. 80 %
IP65
1) with individual calibration on site or Teach-In (type 8025)
≤± 0.5 % o.F.S (*)
2) with K-factor standard
≤± (0.5 % o.F.S + 2,5 % o.R) (*)
≤± 0.5 % o.F.S (*)
0.4 % o.R (*)
2
PVC, PP, PVDF, SS 316L (1.4404) or brass
PVDF; Axis and bearing ceramic
FPM standard (option EPDM)
PC
with coil 1
(ref 423912C)
0.3 to 10 m/s (1.0 to 32.8 ft/s) from 3 l/min (DN15)
None
Alternating 0...10 V, frequency: 0...300 Hz
10 m (shielded cable max. 1,5 mm
with Hall sensor 2
0.3 to 10 m/s (1.0 to 32.8 ft/s)
from 3 l/min (DN15)
12...30 VDC
Transistor NPN/PNP open collector max. 100 mA
Frequency: 0...300 Hz
50 m (shielded cable, max. 1,5 mm
with Hall sensor "low power" 3
0.3 to 10 m/s (1.0 to 32.8 ft/s)
from 3 l/min (DN15)
50 m (shielded cable, max. 1,5 mm
FLOW SENSOR TYPE 8030
(ref 423913D)
(ref 423914E)
E-5-
2
)
2
)
2
)