4 COMMISSIONING
4.2 Commissioning 8030 with adjustable pulse output type 8021
The programming of the Pulse Divider requires the entry of a factor K and a multiplier D.
These parameters are programmed through rotary switches and jumpers (see Fig. 4.1).
To access to electronic board, unscrew central screw and remove cover.
4.2.1 Programming of factor K
Enter the K-factor (pulse/litre) corresponding to fitting DN and material (refer to instruction
manual type S030). To do that, set3 rotary switches and 3 jumpers. Each rotary switch
corresponds to a K- factor digit and each jumper position to a decimal point position.
A K- factor from 0.000 to 999 can be programmed.
Example 1:
K=46,6 puls/l (DN25 PVC)
Programming will be as follows:
0
Example 2:
K=0.517 puls/l (DN150 SS)
Programming will be as follows:
0
Example 3:
K=11,46 puls/l (DN50 SS)
Programming will be as follows:
0
The fourth digit is not taken into account.
!
The factor K must be confirmed by a reset (short-circuit on jumper 8).
0
0
0
0
0
0
FLOW SENSOR TYPE 8030
1, 2, 3 rotary switches for factor K programming.
5, 6, 7 jumpers for decimal position of factor K.
4
rotary switch for multiplier D
programming.
8
reset jumper.
Fig. 4.1 Electronic board TYPE 8021
E-14-