Notices according to DIN EN 179 and DIN EN 1125
!
Warning!
It is hazardous to modify doors along escape routes: The safety features of this product are an essential
requirement for its conformity with DIN EN 179 and DIN EN 1125. Do not make any changes which are not
described in these instructions.
Unsuitable doors reduce personal safety and intrusion protection: Only approved and technically
correct doors are suitable for installation of the multi-point lock 319. Prior to the installation of the multi-
point lock 319, the door must be checked to ensure that it is attached properly and is not warped. The
door must be approved for use of the multi-point lock 319. Door operating elements may not impede each
other.
The multi-point lock 319 is not approved for use on double acting swing doors.
Unsuitable locks impair personal safety and fire protection: The multi-point lock 319 is suitable for fire
doors and smoke protection doors ("Classification key", page 40). Check whether the door certification
matches the lock. Make sure that the multi-point lock 319 is installed in the appropriate size and with the
correct accessories.
Unsuitable door seals impair personal safety: When door seals are used (such as profile seals or bottom
seals), no function of the multi-point lock 319 may be impaired.
Severe injuries can result from broken glass doors: Glass doors or glass parts on doors must be made of
safety glass or composite safety glass.
Unsuitable fastening means reduce personal safety and intrusion protection: Suitable fastening means
must be used depending in the installation situation and materials of the door.
Incorrect or faulty installation impair personal safety: The normal installation height for the horizontal
push rod (panic bar) is 900 mm to 1100 mm above the finished floor surface. If children are present in the
majority of the building, the installation high must be reduced accordingly.
The horizontal push rod must be installed such that the greatest possible effective bar length is achieved.
Any lock counterparts or coverings which are provided should be installed in order to ensure conformity
with this European standard.
Limited movement of the door impairs personal safety: All blocking elements must be installed such
that the free movement of the door is not impeded. Doors may only be secured with the approved locks.
No additional devices may be installed. Any door closers which are installed may not impair the actuation
of the door by children and infirm persons.
EN
37
Information