u Insert the compatible membrane gland (in-
cluded in delivery) into the respective cable
entry point.
Cable entry point
Top side and bottom
side
Rear side
For AMTRON® Compact
2.0 22 and supply line
with an outer diameter
≥ 17 mm only: top side
and bottom side
u Insert the supply line into the product through
the respective cable entry point together with
the control / data line (if applicable).
Approx. 30 cm of cable are required for the
supply line inside the product.
u Fasten the product to the wall using dowels,
screws and sealing plugs. Select the tightening
torque according to the building material of the
wall.
ATTENTION
Material damage due to missing sealing plugs
If the screws in the housing are not covered, or are
not adequately covered with the sealing plugs
provided, the specified protection class is no longer
guaranteed. This can lead to consequential dam-
age of electronic components.
u Cover the screws in the enclosure with the
provided sealing plugs.
u Check the product for firm and secure attach-
ment.
5.6

Electrical connection

The tasks described in this section may only
be carried out by a qualified electrician.
Membrane gland
Membrane gland with
strain relief
Membrane gland
without strain relief
n M25 / M32 adapter
n Locknut
n M32 screw connec-
tion
Tightening torque:
3 Nm

5.6.1 Network configurations

The product can be connected in a TN / TT net-
work.
The product can only be connected in an IT net-
work under the following conditions:
ü Connection to a 230 / 400 V IT network is not
permitted.
ü Connection to an IT network with 230 V ex-
ternal line voltage over a residual current circuit
breaker is permissible, provided that the max-
imum contact voltage does not exceed 50 V AC
when the first error occurs.

5.6.2 Power supply

Fig. 7: Power supply connection
u Strip the supply line.
u Strip the conductors 10 mm.
When routing the supply line, comply with
the permissible bending radius.
Single-phase operation
u Connect the conductors of the supply line to the
terminals L1, N and PE as per the terminal la-
belling.
u Comply with the connection data for the termin-
als.
1 "4 Technical data" [} 10]