Decompression chamber
CAMARA DE DESCOMPRESION
Rock wool insulation
AISLAMIENTO LANA DE ROCA
Protect the inner
PROTEGER LAS PARTES
walls of the wook
INTERNAS DE LA MADERA
Rock wool insulation
AISLAMIENTO LANA DE ROCA
4.3.

CHIMNEY COWL

The chimney draft also depends on the chimney cowl.
The chimney cowl should assure the smoke discharge even during windy days, having into account that it must exceed the top of the roof
(drawing D32).
The chimney cowl must comply with the following requirements:
It must have the same interior section of the chimney.
It must have a usable exit section that is two times the one of the interior of the chimney.
It must be constructed so that the rain, snow or any other objet do not enter inside.
It must be easily accessible in order to do servicing and cleaning tasks.
It the chimney cowl is metallic, due to its own design adapted to the diameter of the pipe, the smoke discharge is assured. There are different
models of metallic chimney cowl, fixed, anti-return, and rotary or extractor.
(1) Industrial chimney of
prefabricated elements
that allow a good smoke
extraction
D32
5.

OUTSIDE AIR INTAKE

For the proper operation of the insert, it is essential that there is air enough for the combustion and re/oxygenation of the environment where it
is installed. In the case of houses built under the requirements of "energy efficiency" with a great degree of air tightness, it is possible that the
air intake is not guaranteed *the fitter must assure compliance with the Technical Building Code. This means that the air must be able to move
for the combustion through some openings connected to the exterior, even when doors and windows are closed. Moreover, it must comply
with the following requirements:
INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS
Metallic channel
CONDUCTO METALICO
maximum inclination 45º
MAXIMA INCLINACION 45º
50 cm
Grate
REJILLA
Exit grate of the convection air
REJILLA SALIDA AIRE CONVECCION
Cold air entry
ENTRADA AIRE FRIO
Rock wool insulation
AISLAMIENTO LANA DE ROCA
5 cm
Space between the pipe and
ESPACIO ENTRE EN TUBO Y
the sealed channel
EL CONDUCTO SELLADO
Grate
REJILLA
Space between the cladding and the insert
ESPACIO ENTRE EL REVESTIMENTO Y EL INSERT
5 mm
Cold air entry
ENTRADA AIRE FRIO
Cold air entry
ENTRADA AIRE FRIO
Wall
PARED
D31
D38
(2) Traditional chimney. The
proper exit section must be,
at least, two times the interior
section of the chimney, the best
is 2,5 times.
(3) Chimney with interior cone
smoke deflector.
27
HYDRO RANGE