Setting of proportional cooling band
MAX
value
This parameter indicates the proportional band applied to the cooling set; this band produces the opti-
mised management of the compressor, only switching it on if the inlet/outlet water temperature (depen-
20 °C
ding on the type of control set by parameter (0) in the installer menu) is greater than the cooling work
set (parameter (1) user menu) plus the value of this parameter.
Setting heating mode temperature set
Value
MAX
This parameter indicates the active work set value in the heating mode. This
parameter is displayed in the cooling only units but cannot be modified.
(*):
(*)
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes
70°C in order to allow insertion of a set-point for boiler adjustment;
Setting of proportional heating band
MAX
value
This parameter indicates the proportional band applied to the heating set; this band produ-
ces the optimised management of the compressor, only switching it on if the inlet/outlet water
20 °C
temperature (depending on the type of control set by parameter (0) in the installer menu) is
less than the heating work set (parameter (3) user menu), minus the value of this parameter.
In cooling only units, this parameter is displayed but it cannot be modified.
Settings made on the basis of outside temperature
MAX
value
This setting activates the algorithm of compensation of the work setting:
SF1
SET (F)
SF2
SET (H)
0
3
SF1: index (6) user menu;
SF2: index (8) user menu;
TF1: index (7) user menu;
TF2: index (9) user menu;
In cooling mode, the work setting is cal-
culated automatically on the basis of the
outside temperature, following the logic
highlighted in the diagram.
Parameter function
Parameter function
Parameter function
Parameter function
SET (G)
SET (I)
(°C)
TF1
TF2
Parameter visible ONLY on units with condensation control
device on board
Parameter ONLY visible on units fitted with twin compressor
Parameter ONLY visible on units fitted with inverter com-
pressor
SET (J)
SC1
SC2
SET (N)
SET (L)
TC1
TC2
SET (O)
SC1: index (A) user menu;
SC2: index (C) user menu;
TC1: index (B) user menu;
TC2: index (d) user menu;
In heating mode, the work setting is cal-
culated automatically on the basis of the
outside temperature, following the logic
highlighted in the diagram.
(°C)